Configuration
821XKlimaBA0399 7-7
Code IMPORTANTPossible settingsNameCode IMPORTANT
InfoSelectionLenze
Name
C018
¤
Chopper
frequency
-1- -0- 4kHz reduced power loss
-1- 8kHz reduced power loss
-2- 12kHz reduced power loss
-3- 16kHz reduced power loss
-4- 4kHz reduced noise emission
-5- 8kHz reduced noise emission
-6- 12 kHz reduced noise emission
-7- 16 kHz reduced noise emission
C019 Threshold auto
DC brake
0.10 0.00 {0.02Hz} 5.00 *depends of the
unit
C021 Slip
0.0 -50.0 {0.1 %} 50.0 *when
compensation
C014 = 2. 3
0.0 0.0 {0.1 %} 20.0 *when C014 = 4
*depends of the
unit
C022 I
max
limit
motor mode
150 30 {1 %} 150
C023 I
max
limit
generator mode
80 30 {1 %} 150 The current-limit
controller for
operation in
generator mode is
not active at
30 %.
C026* Offset adjustment
analog input
0.00 -10.00 {0.01 V} 10.00
C027* Scaling factor of
analog input
100.0 -200.0 {0.1 %} 200.0
C034
¤
Master current -0- -0- 0 to 20mA /
0to5V/0to10V
-1- 4 to 20mA
C035*
¤
Selection DC
brake
-0- -0- Selection of brake voltage under C036
-1- Selection of brake current under C036
C036 Voltage for DC
brake
* 0 {0.02 %} 150 *depends on the
unit
C037 JOG value 1 20.00 -480.00 {0.02Hz} 480.00
C038 JOG value 2 30.00 -480.00 {0.02Hz} 480.00
C039 JOG value 3 40.00 -480.00 {0.02Hz} 480.00
C040 Controller enable * -0- Controller inhibited
-1- Controller enabled
*see Operating
Instructions TB
2102
C043 TRIP reset * -0- No current fault
-1- Current fault
*see Operating
Instructions 2102
C046 Frequency
setpoint
* -480.00 {0.02 %} 480.00 *see Operating
Instructions 2102