Technical data
General data and operating conditions
3
53
EDK94AMH24 DE/EN/FR/ES/IT 1.0
3 Technical data
3.1 General data and operating conditions
Supply system data
Supply forms
With earthed neutral
Unrestricted use
IT systems Observe instructions about special measures!
Noise emission EN 61800-3
Cable-guided: c annot be specified because dependent on the
conditions present in the interconnected system
Radiation: category C3
Noise immunity EN 61800-3 Category C3
Standards
Conformity CE
Low-Voltage Directive (73/23/EEC)
Approval UL 508C Power Conversion Equipment (file no. 132659)
Protection
Enclosure
EN 60529
IP 20
Not in the wire range of
the terminals on the
motor side
NEMA 250 Protection against contact to
type 1
Insulation resistance EN 61800-5-1 Overvoltage category III
Derating at and above 2000 m: overvoltage category II
Discharge current EN 61800-5-1 >3.5mA Observe regulations and
safety instructions!
Environmental conditions
Climate
Storage
IEC/EN 60721-3-1 1K3 (-25 ... +60 °C)
Transport IEC/EN 60721-3-2 2K3 (-25 ... +70 °C)
Operation IEC/EN 60721-3-3 3K3 (-10 ... +55 °C)
Power derating at +45 ... +55 °C: 2.5 %/°C
Site altitude 0 ... 4000 m amsl
Power derating at 1000 ... 4000 m amsl: 5 %/1000 m
Pollution EN 61800-5-1 Pollution degree 2
Vibration resistance Germanischer Lloyd General conditions: acceleration resistant up to 0.7 g