Connecon acc
ording to UL
Important notes
WARNING!
UL/CSA marking
Secondary circuit shall be supplied from an external isolang sour
ce.
Maximum surrounding air temperature is 45 °C.
Maximum surrounding air temperature with derang is 55 °C.
Marquage UL/CSA
Le circuit auxiliaire doit être alimenté par une source de tension externe isolée
galvaniquement.
Température ambiante maximale : 45 °C.
Température ambiante maximale avec dèclassement : 55 °C.
WARNING!
UL marking
The supply shall be derived from a non-corner grounded type TN AC source not exceeding
277 V phase t
o earth.
Marquage UL
Lalimentaon triphasée doit provenir d’une source de type TN ne dépassant pas 277 V
entre phase et terre.
WARNING!
UL marking
Drives shall be used with line reactor connected in series with AC mains, all rated min.
480 V
.
Lenze type designaon see table below.
Marquage UL
Les variateurs avec une tension assignée mini de 480 V doivent être ulisés avec une
inductance de ligne raccordée en série à un réseau électrique triphasé.
Se reporter au tableau ci-dessous pour connaître les désignaons de type Lenze.
Electrical ins
tallaon
Connecon according to UL
Important notes
128