Terminal data
Rated power P
r
ated
kW 0.37 ... 2.2 4 ... 5.5
Connecon descripon Mains connecon
Connecon X100
Connecon type Pluggable
Max. cable cross-secon mm² 2.5 16
Max. cable cross-secon AWG 12 6
Stripping length mm 8 14
Stripping length in 0.3 0.55
Tightening torque Nm 0.5 1.8
Tightening torque lb-in 4.4 16
Required tool Screwdriver 0.5 x 3.0 Screwdriver 0.8 x 4.0
Rated power P
r
ated
kW 0.37 ... 2.2 4 ... 5.5
Connecon descripon PE connecon
Connecon PE screw
Max. cable cross-secon mm² 6 16
Max. cable cross-secon AWG 10 6
Stripping length mm 10 11
Stripping length in 0.4 0.4
Tightening torque Nm 2 3.4
Tightening torque lb-in 18 30
Required tool Torx key 20 Crossp screwdriver PZ2
Rated power P
r
ated
kW 0.37 ... 2.2 4 ... 5.5
Connecon descripon Motor connecon
Connecon X105
Connecon type Pluggable
Max. cable cross-secon mm² 2.5 16
Max. cable cross-secon AWG 12 6
Stripping length mm 8 14
Stripping length in 0.3 0.55
Tightening torque Nm 0.5 1.8
Tightening torque lb-in 4.4 16
Required tool Screwdriver 0.5 x 3.0 Screwdriver 0.8 x 4.0
The terminal data for the terminal X1 can be found under:4Basic Sa
fety - STO ^ 161
The terminal data for the terminals X82 and X83 can be found under: 4Terminal data ^ 165
Electrical ins
tallaon
Mains connecon