Technical data
General data and operating conditions
3
l
41
EDK94ARN24 ZH/EN 2.1
Mounting conditions
Mounting place
In the control cabinet
Mounting position Vertical
Mounting clearances
Above/below
³ 80 mm / ³ 120 mm
Observe the device−related
notes on mounting.
To the sides
Side−by−side mounting without
any clearance
Supply conditions for the regenerative power supply module
AC mains operation
Connection at the assigned mains filter
DC−bus operation Direct connection of the axis modules via terminals or
busbar systems
See the chapter on DC−bus operation in the Hardware
Manual for further information.
Environmental conditions
Climate
Storage
IEC/EN 60721−3−1 1K3 (−25 ... +60 °C)
Transport IEC/EN 60721−3−2 2K3 (−25 ... +70 °C)
Operation IEC/EN 60721−3−3 3K3 (−10 ... +55 °C)
Current derating at +45 ... +55 °C: 2.5 %/°C
Site altitude 0 ... 4000 m amsl
1000 ... 4000 m amsl: current derating of 5 %/1000 m
Pollution EN 61800−5−1 Pollution degree 2
Vibration resistance (9.81 m/s
2
= 1 g)
Transport
IEC/EN 60721−3−2 2M2
EN 61800−2
2 ... 9 Hz: amplitude 3.5 mm
10 ... 200 Hz: acceleration resistant up to 10 m/s
2
200 ... 500 Hz: acceleration resistant up to 15 m/s
2
Operation
Germanischer Lloyd 5 ... 13.2 Hz: amplitude ±1 mm
13.2 ... 100 Hz: acceleration resistant up to 0.7 g
IEC/EN 60068−2−6
10 ... 57 Hz: amplitude 0.075 mm
57 ... 150 Hz: acceleration resistant up to 1 g