Technical data
Electrical data
3
l
42
EDK94ARN24 ZH/EN 2.1
3.2 Electrical data
Basis of the data
Mains Voltage Voltage range Frequency range
U
LN
[V] U
LN
[V] f [Hz]
3/PE AC 230 180 − 0 % ... 264 + 0 % 45 − 0 % ... 65 + 0 %
3/PE AC 400 320 − 0 % ... 440 + 0 % 45 − 0 % ... 65 + 0 %
3/PE AC 500 400 − 0 % ... 550 + 0 % 45 − 0 % ... 65 + 0 %
Input data (on the supply side)
Voltage Frequency Current [A]
Number of
phases
[V] [Hz] max. +45 °C max. +55 °C
E94ARNE0134
In motor mode
230/400/500 50/60 26/26/26 19.5/19.5/19.5 3
In generator mode
230/400/500 50/60 13/13/13 9.8/9.8/9.8 3
E94ARNE0244
In motor mode
230/400/500 50/60 47/47/47 35/35/35 3
In generator mode
230/400/500 50/60 23.5/23.5/23.5 17.6/17.6/17.6 3
Temperature in the control cabinet
Voltage Continuous input power
Type [V] S
L
[kVA]
E94ARNE0134
In motor mode
230/400/500 10.3/18.0/22.5
In generator mode
230/400/500 5.2/9.0/11.2
E94ARNE0244
In motor mode
230/400/500 18.7/32.5/40.7
In generator mode
230/400/500 9.4/16.3/20.3