Technical data
Rated data
2
l
50
EDKLCMZ3024−SPS DE/EN 4.0
) Note!
The motor starters are designed for motor powers between 0.75 kW and 3 kW
and rated currents between 1 A and 7 A.
If motors with powers < 0.75 kW or rated currents < 1 A are operated on the
motor starters, please observe the following:
ƒ The internal I
2
xt monitoring cannot be used because of the low current.
Switch off the internal I
2
xt monitoring (C0121 = 0).
Use a PTC or thermal contact (NC contact) to monitor the motor
temperature
Appropriate external motor protection switches can be used in addition.
ƒ The mains phase failure control can respond during operation, although no
main failure has occurred.
Deactivate the mains phase failure control (C0122 = 3) to ensure that the
drive will not switch off with an error message.