Technical data
Rated data
2
l
49
EDKLCMZ3024−SPS DE/EN 4.0
Deviating valuesValuesOperating conditions
below
connectors used and the cable bending radii.
to the sides
2.2 Rated data
Motor starter type ELCAMZI 7514SNNPSNN 1524SNNPSNN 2224SNNPSNN 3024SNNPSNN
Supply voltage (safely separated power supply unit SELV/PELV)
Voltage range U
DC
+ 24 V DC (+20 V DC − 0% ... +26.5 V DC + 0%)
Current consumption at + 24 V
DC
Min. 1 A (no digital inputs and outputs connected)
Max. 5 A (all digital inputs and outputs connected)
Motor switch
Mains voltage
(switched voltage)
U
N
3/PE AC 320 V − 0% ... 530 V + 0%; 45 Hz − 0% ... 65 Hz + 0%
Cyclic switching Max. 600 switchings / h
Cable protection 16 A, integrated into the housing
Max. motor power
(total power f connected Lenze
motors)
P
N
[kW] 0.75 1.5 2.2 3.0
Max. continuous output
current
(sum of the output currents)
I
N
[A] 2.0 3.5 5.0 7.0
Brake switch (AC3 contact)
Output voltage U
B
= mains voltage
Max. output current I
B
[A] 0.4
Cyclic switching Max. 600 switchings / h
Control connections
Digital inputs 4 (X41, X42)
Digital outputs 2 (X45)
Safe inputs 4 (X60)
Safe outputs 2 (X60)
Manual operation 1 (X72)
Sum of all input currents and
output currents on X41, X42,
X45, X60, X72
[A] Max. 1.3
Monitoring functions
Motor protection switch I
2
t monitoring, tripping classes adjustable
(I
2
t tripping trait: ^ 51)
max. I
r
class 10A [A] 2.0 3.5 5.0 7.0
max. I
r
class 10 [A] 1.7 3.3 4.8 6.5
max. I
r
class 20 [A] 1.5 3.0 4.4 6.0
max. I
r
class 30 [A] 1.3 2.5 3.8 5.0
Motor temperature PTC thermistor (PTC) or thermal contact (NC contact)
Device protection I
2
t monitoring class 10A,
relating to max. continuous output current
Mains failure control Yes
Load failure control Yes, programmable switch−off limit
Mass Approx.
[kg]
5.5 5.5 5.5 5.5