Electrical installation
Important notes
4
l
54
EDKLCMZ3024−SPS DE/EN 4.0
4 Electrical installation
4.1 Important notes
) Note!
ƒ Please keep the plastic covers on the connectors for the control connections
and interfaces!
ƒ Cover unused connections during transport, storage and operation with the
plastic covers to preserve the certified safety engineering features.
{ Danger!
ƒ The X2x power connector contacts can conduct hazardous voltages if the
motor starter is connected to the mains. Therefore, disconnect the motor
starter before carrying out any work on it.
ƒ All control terminals feature only basic insulation (single isolating distance)
following the connection of a PTC thermistor (PTC) or a thermal switch (NC
contact):
– Protection against accidental contact with defective isolating distance can
only be ensured through external measures, e.g. double insulation.
ƒ To avoid injury to persons and breakdowns, it is essential that the motor
starter is properly earthed via X10!
( Stop!
Ensure trouble−free operation of the motor starter:
ƒ Avoid compensating currents via the PROFIBUS cable shield:
– For this, connect all devices with a 16 mm
2
cable via the FE bolts.
– Lay cable in parallel to bus cable.
– Use a copper braid cable to connect the FE bolts with the mounting
surface.
ƒ Properly lock the connector plugs.
EMC−compliant wiring
) Note!
ƒ Use a copper braid cable to connect the PE bolt with the mounting surface.
ƒ Separate control and data cables from motor cables.
ƒ Connect control and data cable shields at both ends.