Electrical installation
Communication
4
l
66
EDKLCMZ3024−SPS DE/EN 4.0
lcu121_000i
X31 − PROFIBUS input
Pin Signal Description Data
Connector: male, 5−pin, M12, B−coded
1 n. c. Not assigned
PROFIBUS−DP−V1
Max. 12 Mbps
2 A Data line A
3 n. c. Not assigned
4 B Data line B
5 Shld Shield
X32 − PROFIBUS output
Pin Signal Description Data
Connector: female, 5−pin, M12, B−coded
1 VP +5 V for bus termination
PROFIBUS−DP−V1
Max. 12 Mbps
Bus termination via separate bus
terminating connector
2 A Data line A
3 GND Reference potential for bus termination
4 B Data line B
5 Shld Shield
) Note!
Plug the bus terminating connector on the last bus station to ensure
trouble−free operation of the PROFIBUS.