-101-
Does the operating LED in display PCB
Ass'y blink 11 times?
When compressor does not operate normally.
■ High press Error (Error Code )
Trouble 7-5
YES
Is the installation condition of outdoor unit
right.
Check the installation condition.
NO
YES
Is the indoor/outdoor fan locked?
Check the indoor/outdoor fan motor.
NO
YES
Is the refrigerant pressure right? Remove or supply the refrigerant.
NO
YES
Replace the PCB Ass'y.
• Main PCB Ass'y (Outdoor)