101
Pre-Commissioning
Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
MODBUS PROTOCOL REGISTERS
Discrete Register
Register Address Meaning
10001 Reserve
10002
0 : Load Water Flow Switch Off
1 : Load Water Flow Switch On
10003 Reserve
10004
0 : Load Water Pump Output Off
1 : Load Water Pump Output On
10005 Reserve
10006
0 : Load Water Pump Interlock Off
1 : Load Water Pump Interlock On
10007~10104 Reserve
10105
0 : Cycle 1's 4 Way Valve 1 Off
1 : Cycle 1's 4 Way Valve 1 On
10106
0 : Cycle 1's 4 Way Valve 2 Off
1 : Cycle 1's 4 Way Valve 2 On
10107
0 : Cycle 1's Hot gas1 Off
1 : Cycle 1's Hot gas1 On
10108
0 : Cycle 1's Hot gas2 Off
1 : Cycle 1's Hot gas2 On
10109
0 : Cycle 1's Sump Heater 1 Off
1 : Cycle 1's Sump Heater 1 On
10110
0 : Cycle 1's Sump Heater 2 Off
1 : Cycle 1's Sump Heater 2 On
10111~10118 Reserve
10119
0 : Cycle 1's Inverter Compressor 1 Off
1 : Cycle 1's Inverter Compressor 1 On
10120
0 : Cycle 1's Inverter Compressor 2 Off
1 : Cycle 1's Inverter Compressor 2 On
10121~10208 Reserve