13
Product Data
Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
SPECIFICATIONS
Table 2: Specication Data for 460V Heat Pump Chiller.
ACHH017HBAB ACHH020HBAB ACHH033HBAB ACHH040HBAB
Phase, Lines, V,Hz
RT
16.2 18.5 32.42 37
kBtuh/h
194.5 222 389 444
Heang
kBtuh/h
204.5 239 409 478
Cooling
kW
18.1 21.5 36.2 43.0
Heang
kW
19.1 22.6
38.1 45.2
Cooling
EER btuh/W
10.75 10.33 10.75 10.33
Heang
COP
3.15 3.1 3.15 3.1
btuh/W 19.46
19.46
19.46 19.46
Sound Power Cooling
dB(A)
78 83 86 87
Sound Pressure 30' Cooling
dB(A)
49 51 52 54
Sound Pressure 5' Cooling
dB(A)
69 71 72 74
Sound Power Heang
dB(A)
83 83 86 87
Sound Pressure 30' Heang
dB(A)
49 51 52 54
Sound Pressure 5' Heang
dB(A)
69 71 72 74
No. of Compressors
EA
2 2 4 4
Oil Charge Each Compressor
OZ/EA 33.8 33.8 33.8 33.8
Amount of Charge EA Circuit
lbs/EA 15.4 15.4 15.4 15.4
Quanty EA 1 1 2 2
Pressure Drop psi 2.7 3.1 2.7 3.1
Operang Maximum Pressure
(Refrigerant/Water)
psi 597/142 597/142 597/142 597/142
Cooling Water Flow (10F Delta) GPM 38.9 44.4 77.8 88.7
Inlet/Outlet Water Connecon inches/ange 2"/150 lb 2"/150lb 2 1/2"/150lb 2 1/2"/150lb
No. of Fan Motors
EA
2 2 4 4
No. of Blades per Fan
EA
4 4 4 4
Air Flow Rate
CFM/EA
8684 8684 8684 8684
Motor Power
W/EA
1500 1500 1500 1500
W
inches
30 1/8 30 1/8 60 5/8 60 5/8
H
inches
86 5/8 86 5/8 86 5/8 86 5/8
D
inches
84 13/16 84 13/16 84 13/16 84 13/16
High/Low Pressure
Electronic
Flow Switch
Paddle/ADJ.
Freeze Protecon
On/O Contact Only
Cooling
F
Approved Water Delta T
Cooling and Heang
F
Cooling
F
Guaranteed Load Capacity Range
Remote Monitoring and Control
Range
Operaonal Range
Dimensions
Protecon Devices
Fan Motor
Refrigerant
Evaporator
Input Power
Inverter Scroll Chiller Model
Capacity
Cooling
Eciency
Compressor
Heat Trace Elements and Power by Others