23
Product Data
Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
REFRIGERANT PIPING AND SENSOR DIAGRAM /
OPERATION RANGE AND LIMIT
1. Proper Glycol Solution is required for Ambient
Operation at or below 41
F
2. LG LATS ISC Selection Software is to be used to
confirm selection and performance.
F LWT (-22F/30%, 17F/100%)
F LWT (-4F/65%, 32F/100%)
F LWT (14F/70%, 32F/100%)
F LWT (17F/70%, 41F/100%)
% of Rated Capacity
105
95
85
ACHH Hot Water Operation Limits and Performance
145
135
125
115
30 40 50 60
75
65
55
-20 -10 0
Approved Δ between EWT and LWT is 4°F to 20°F
Heating Capacity Performance 10°ΔT (EWT to LWT)
100%
90%
70 80 90 100
Ambient Air Degrees F
Operation Range
HOT Water Inlet
Temperature F
66°F to 127°F
HOT Water Outlet
Temperature F
86°F to 131°F
10 20
90 100-10 0 10 20 30 40
Ambient Air Degrees F
70%
60%
LWT
and
EWT
HOT Water Temperature Degrees F
50 60 70 80
80%
50%
40%
30%
20%
-20
Ambient Range
-22°F to 95°F