EasyManua.ls Logo

LG LS-E0960CL - Test Running and Performance Evaluation; Power Connection and Remote Setup; Outdoor Unit Mounting and Performance Check

LG LS-E0960CL
70 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
-36-
A
Oil trap
Outdoor unit
Indoor unit
B
A
B
Outdoor unit
Indoor unit
7. Pipe length and the elevation
Capicity is based on standard length and maximum allowance length is the basis of reliability.
Oil trap should be installed per 5~7 meters.
Numerical value in "( )" is for Rotary Comp. model.
CAUTION
In case more than 5m
Max. Piping
Length
(m)
Capacity
(Btu/h)
7~12K 15 7 4 20
18K 30(20) 15(10) 4 or 5 40
24K~30K 30 15 4 or 5 40
Max.
Elevation
(m)
Standard
Length(m)
Additional Refrig-
erant
(g/m)