EasyManua.ls Logo

LG LS-H0560CL - Operation Details

LG LS-H0560CL
53 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Operation Details
(1) The function of main control
1. Time Delay Safety Control
3min.; The compressor operation is delayed for 3 minutes to balance the pressure of cycle.
(Protection of compressor)
5sec.;
The indoor fan is delayed for 5 seconds, when operating initially, to prevent noises occurred by the vertical
louver and wind.
2. Airflow Direction Control
This function is to swing the vertical louver up and down automatically and to set it at a fixed position.
The procedure is as the following.
1st ; Press the ON/OFF Button to operate the unit.
2nd ; Press the Airflow Direction Control Button to swing the vertical louver up and down automatically.
3nd ; Repress the Airflow Direction Control Button to set the vertical louver at a fixed position.
3. Cooling Mode Operation
When selecting the Cooling( ) Mode Operation, the unit will operate according to the setting by the
remote controller and the operation diagram is shown below.
CLOSED
8
7
6
5
4
3
2
1
OPEN
Setting point:
8°
108°
INTAKE AIR TEMP.
SETTING TEMP. +0.5°C
(Compressor ON)
SETTING TEMP. -0.5°C
(Compressor OFF)
More than
3 minutes
More than
3 minutes
INDOOR FAN SPEED
COMPRESSOR
Selecting
fan speed
Selecting
fan speed
Selecting
fan speed
Low
ON OFF ON ONOFF
Low
9

Related product manuals