34
Single Zone Extended Piping Wall Mounted Installation Manual
Due to our policy of continuous product innovation, some specifications may change without notification.  
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
REFRIGERANT PIPING CONNECTIONS
Outdoor Unit Connections
Outdoor Unit Piping Connections
1.  The HLV3 outdoor unit piping connections are on the side of the 
unit. 
:KHQWLJKWHQLQJWKHÀDUHQXWZLWKDWRUTXHZUHQFKHQVXUHWKHGLUHFWLRQ
for tightening follows the arrow on the wrench.
Table 18: Torque Wrench Tightening.
Pipe Size (in. OD) Outside Diameter (mm) Torque (lbs-ft)
1/4 6.35 13.0 - 18.0
3/8 9.52 24.6 - 30.4
1/2 12.7 39.8 - 47.7
5/8 15.88 45.4 - 59.3
3/4 19.05 71.5 - 87.5
Figure 35: Outdoor Unit Piping 
Connections (HLV3).
Figure 36: Removing the 
Flare Nuts on the Outdoor 
Unit.
Piping 
Connections
Side Panel
Figure 37: Connecting the 
Flared Field Piping to the Out-
door Unit Connection.
The HLV3 outdoor unit has a side panel that covers its electrical compo-
nents. The side panel does not have to be removed for piping installation, 
however, it will need to be removed for power wiring / communication 
(connection) cable installation.
2.  Remove the flare nuts attached to the outdoor unit valves.
3.  Thread the flare nuts onto the field-supplied piping. 
4.  Flare the end of the piping following the information in the 
“General Refrigerant Piping System” section and industry best 
practices.
5.  Place a couple of drops of PVE refrigerant oil on outside of the 
flare before assembling. 
Do not add any contaminants.
6.  Align the center of the refrigerant piping to the corresponding 
outdoor unit connection. 
7.  Connect the field piping to the outdoor unit connection. Tighten 
the flare nut initially by hand.
8.  Finish tightening the flare nut with a torque wrench until the 
wrench clicks. Follow torque guidelines in the table.