GENERAL DATA
Table 2: Single Zone Extended Pipe Indoor Unit Electrical Data
Electrical
Voltage tolerance is ±10%.
Maximum allowable voltage unbalance is 2%.
MSC = Maximum Starting Current.
MCA = Minimum Circuit Ampacity.
Maximum Overcurrent Protection (MOP) is calculated as follows: (Largest motor FLA x 2.25) + (Sum of
other motor FLA) rounded down to the nearest standard fuse size.
Model Number Nominal Tons
Compressor
Qty
Compressor
(A) Cool / Heat
Fan Qty
Outdoor Unit
Fan (A)
MCA (A) MOP (A)
LS243HLV 2 1 14.6 / 14.6 1 0.25 19 30
LS303HLV 2-1/2 1 14.6 / 14.6 1 0.25 19 30
LS363HLV 2-3/4 1 14.6 / 14.6 1 0.25 19 30