INSTALLATION SPACE
17
ENGLISH
Collective / Continuous Installation for roof top use
Space required for collective installation and continuous installation: When installing several units,
leave space between each block as shown below considering passage for air and people.
1. One row of stand alone installation
350 or
more
2 000 or
more
600 or
more
1 000 or
more
2. Rows of collective installation (2 or more)
• L should be smaller than H
L
350 or
more
3 000 or
more
H
600 or
more
1 500 or
more
100 or
more
L H
[Unit:mm]