14 _ Ceiling Concealed Duct_Built in (Low Static)
Indoor Units
8. Electric Characteristics
Symbols:
MCA : Min, Circuit Amps(A)
MFA : Max. Fuse Amps(see note 5)
kW : Fan Motor Rated Output(kW)
FLA : Full Load Amps(A)
IFA : Indoor Fan Motor
Note :
1. Voltage range
Units are suitable for use on electrical systems where volt-
age supplied to unit terminals is not below or above listed
range limits,
2. Maximum allowable voltage unbalance between phases is
2%
3. MCA/MFA
MCA=1.25 x FLA
MFA≤ 4 x FLA
(Next lower standard fuse rating. Min. 15A)
4. Select wire size based on the MCA
5. Instead of fuse, use Circuit Breaker.
Units
Model
Type Hz Volts
Voltage Range
ARNU07GB3G4+PBSGB30(Acc'y), PBSC30(Acc'y) B3 1.00 15 85 85
ARNU09GB3G4+PBSGB30(Acc'y), PBSC30(Acc'y) B3 1.00 15 85 85
ARNU12GB3G4+PBSGB30(Acc'y), PBSC30(Acc'y) B3
50 220-240
Max:264 1.00 15 85 85
ARNU15GB3G4+PBSGB30(Acc'y), PBSC30(Acc'y) B3 Min:198 1.00 15 85 85
ARNU18GB4G4+PBSGB40(Acc'y), PBSC40(Acc'y) B4 1.20 15 115 115
ARNU24GB4G4+PBSGB40(Acc'y), PBSC40(Acc'y) B4 1.20 15 115 115
ARNU07GB3G4+PBSGB30(Acc'y), PBSC30(Acc'y) B3 1.00 15 85 85
ARNU09GB3G4+PBSGB30(Acc'y), PBSC30(Acc'y) B3 1.00 15 85 85
ARNU12GB3G4+PBSGB30(Acc'y), PBSC30(Acc'y) B3
60 220
Max:242 1.00 15 85 85
ARNU15GB3G4+PBSGB30(Acc'y), PBSC30(Acc'y) B3 Min:198 1.00 15 85 85
ARNU18GB4G4+PBSGB40(Acc'y), PBSC40(Acc'y) B4 1.20 15 115 115
ARNU24GB4G4+PBSGB40(Acc'y), PBSC40(Acc'y) B4 1.20 15 115 115
Power Supply IFM Input(W)
MCA MFA kW FLA Cooling Heating
0.024 0.76
0.024 0.76
0.024 0.76
0.024 0.76
0.038 0.97
0.038 0.97
0.024 0.76
0.024 0.76
0.024 0.76
0.024 0.76
0.038 0.97
0.038 0.97