4 _ Ceiling Concealed Duct(Middle Static)
Indoor Units
 Type
 Model                               Unit
                                                                       kW
 Cooling Capacity                                         kcal/h
                                                                      Btu/h
                                                                       kW
 Heating Capacity                                         kcal/h
                                                                      Btu/h
 Casing  
 
Dimensions(WxHxD)
 
Body
                                 mm
                                                                       inch
 
Coil
 
Rows x Columns x FPI
 
                             Face Area                          m
2
                             Type  
 
Motor Output x Number           
W
                             Running Current                 A
 
Air Flow Rate(H / M / L)
       CMM
 
(High Mode-factory set)
        cfm
 Fan  
External Static Pressure
 mmAq(Pa)
 
Air Flow Rate(H / M / L)
       CMM
                             (Standard Mode)               cfm
 
External Static Pressure
 mmAq(Pa)
                             Drive  
                             Motor type  
 Temperature Control  
 Sound Absorbing Thermal Insulation Material
 Air Filter
 Safety Device  
 
 
Liquid Side                    mm(inch)
 
Pipe Connections
  Gas Side                       mm(inch)
 
Drain Pipe(Internal Dia.)
     mm(inch)
 Net Weight   Body                              kg(lbs)
 
Noise Level
(Sound Pressure, 1.5m, H / M / L)
       dB(A)
 Power Supply                                            Ø, V, Hz
 Refrigerant Control 
  Transmission Cable                                    mm
2
Ceiling Concealed Duct - Middle Static
  ARNU28GM2A4   ARNU36GM2A4    ARNU42GM2A4 
                  8.2                                     10.6                                    12.3
                7,100                                  9,100                                 10,600
               28,000                                36,200                                42,000
                  9.2                                     11.9                                    13.8
                8,000                                 10,200                                11,800
               31,500                                40,600                                47,000
  Galvanized Steel Plate       Galvanized Steel Plate      Galvanized Steel Plate
      1250 × 270 × 700               1250 × 270 × 700              1250 × 270 × 700
  49-7/32 x 10-5/8 x 27-9/16      49-7/32 x 10-5/8 x 27-9/16      49-7/32 x 10-5/8 x 27-9/16
            2 x 13 x 18                          2 x 13 x 18                         3 x 13 x 18
                 0.31                                    0.31                                    0.31
           Sirocco Fan                        Sirocco Fan                       Sirocco Fan
              350 x 1                               350 x 1                               350 x 1
                  2.3                                      2.3                                      2.3
       28.0 / 24.0 / 21.0                32.0 / 28.0 / 24.0                38.0 / 33.0 / 28.0
        989 / 848 / 742                  1130 / 989 / 848                1342 / 1165 / 989
                6(59)                                   6(59)                                  6(59)
       28.0 / 24.0 / 21.0                32.0 / 28.0 / 24.0                38.0 / 33.0 / 28.0
        989 / 848 / 742                  1130 / 989 / 848                1342 / 1165 / 989 
                5(49)                                   5(49)                                  5(49)
                Direct                                  Direct                                 Direct
                BLDC                                  BLDC                                 BLDC
Microprocessor, Thermostat for cooling and heating
     Foamed polystrene            Foamed polystrene            Foamed polystrene
                    -                                          -                                         -
                Fuse                                   Fuse                                   Fuse
            Ø9.52(3/8)                          Ø9.52(3/8)                         Ø9.52(3/8)
           Ø15.88(5/8)                        Ø15.88(5/8)                       Ø15.88(5/8)
                25(1)                                   25(1)                                  25(1)
              38.0(84)                              38.0(84)                             39.5(87)
           36 / 34 / 33                         37 / 36 / 34                         38 / 37 / 36
  1, 220-240, 50                    1, 220-240, 50    1, 220-240, 50  
  1, 220, 60    1, 220, 60     1, 220, 60  
                 EEV                                    EEV                                   EEV
   CVV-SB 1.0~1.5 x 2C        CVV-SB 1.0~1.5 x 2C        CVV-SB 1.0~1.5 x 2C
Notes:
1. Capacities are based on the following conditions:
    Cooling    • Indoor temp. 27°C[80.6°F]DB/ 19°C[66.2°F]WB
                     • Outdoor temp. 35°C[95°F]DB/ 24°C[75.2°F]WB
                     • Interconnecting Piping Length 7.5m
                     • Level Difference of Zero
    Heating    • Indoor temp. 20°C[68°F]DB/ 15°C[59°F]WB
                     • Outdoor temp. 7°C[44.6°F]DB/ 6°C[42.8°F]WB
                     • Interconnecting Piping Length 7.5m
                     • Level Difference of Zero
2. Capacities are net capacities
3. Due to our policy of innovation some specifications may be changed without prior notification
4. Wiring cable size must comply with the applicable local and national codes. And “Electric characteristics”
chapter should be considered for electrical work and design. Especially the power cable and circuit breaker
should be selected in accordance with that.
4. EEV : Electronic Expansion Valve
5. Sound pressure levels are measured at 50Pa External Static Pressure condition.
6. Anechoic chamber conversion value is measured at 1.5 m downward from unit centre. 
The values depends on the ambient conditions and values are normally higher in actual operation.
Conversion Formula
kcal/h= kW x 860
Btu/h = kW x 3412
cfm = m
3
/min x 35.3
l/s = CMM x 1000/60