38 Outdoor Unit
Refrigerant piping installation
Branch pipe Fitting
Y branch
A
B
To outdoor unit
To branch piping or indoor unit
A
B
Facing
upwards
Facing
downwards
Within ± 3° Within ± 3°
Viewed from point A
in direction of arrow
Horizontal
plane
Within +/- 10°
A
Insulator
(included with kit)
Liquid and gas
pipe joints
Insulator for
field piping
Tape
(field supply)
Ensure that the branch pipes are attached horizontally or vertically (see the diagram below.)
There is no limitation on the joint mounting configuration.
If the diameter of the refrigerant piping selected by the procedures described is different from the size
of the joint, the connecting section should be cut with a pipe cutter.
Branch pipe should be insulated with the insulator in each kit.