EasyManua.ls Logo

LG Multi V ARUB Series - Page 58

LG Multi V ARUB Series
81 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
58 Outdoor Unit
HR Unit PCB
'88' is displayed on outdoor unit main PCB and
HRunit PCB
Completion of auto addressing
The number of the indoor units connected is
displayed at 7-SEG of the outdoor unit main PCB
after 2~7 minutes
The number of HR units connected is displayed
at 7-SEG of the outdoor unit main PCB
Are the number
of indoor units connected to the outdoor unit
wiring and displayed one equal?
Turn HR unit , indoor unit and outdoor unit on in
the order named.
Wait for 3 minutes
Check power and communication wiring between
outdoor, HR and indoor units
Retry indoor unit auto-addressing after checking
trouble
Incompletion of auto addressing
Press SW02M of the outdoor unit main PCB for 5
seconds
Yes
No
Flow chart for addressing of indoor and HR Unit
1) Flow chart for Auto addressing

Other manuals for LG Multi V ARUB Series

Related product manuals