Installation Manual 115
New Function
SW_
STEP
Input_1 Input_2 Input_3
Comp capacity
Of outdoor unit(%)
0
0 0 0 No control
1 0 0 70
0 1 0 40
0 0 1 COMP OFF
1
0 0 0 No control
1 0 0 70
0 1 0 50
0 0 1 COMP OFF
2
0 0 0 No control
1 0 0 80
0 1 0 50
0 0 1 COMP OFF
3
0 0 0 No control
100 70
0
10 40
00
1 ALL OFF
4
0 0 0 No control
100 70
0
10 50
00
1 ALL OFF
5
0 0 0 No control
100 80
0
10 50
00
1 ALL OFF
6
0 0 0 No control
100 50
0
1 0 COMP OFF
00
1 ALL OFF
- Using Analog signal with DDC Module
Non
Control
100%
90%
80%
70%
60%
50%
45%
40%
0V 1V 2V 3V 4V 5V 6V 7V 8V 9V 10V
01234567 8 910
Comp.
OFF
System
OFF
Signal
Input
Step
Performance output of the ODU