Installation Manual 93
Test Run
Integrated Test Running Function_Heating Mode (Setting 4)
Start
Yes
No
Note 1
Error Display
End
Completed
Press the black button for 2 sec.
after turning off all of Dip switch.
Error Display
(All-1) IDU operation
1 IDU operation
Oil return operation
System off
All IDU operation data(10min)
Temp. Condition
Press the black button for 2 sec.
This function is checking process for normal operation of parts and system On operating system.
All processes carry out included refrigerant amount judge logic and check normal condition of parts on heating
mode.
This function check only normal condition of parts on heating mode.
• Saved data can check using LGMV.
Note
1. Judge the normal condition refer to report of Test Running.
DIP Switch Settings
Warning : Please reset Main PCB before starting this function