Installation Manual 95
Test Run
Night Low Noise Function
In cooling mode, this function makes the ODU fan operate at low RPM to reduce the fan noise of ODU at night
which has low cooling load.
Max. RPM setting method
Example of Max. RPM Setting
Setting Method for Fan Max. RPM
CAUTION
1. Request installer to set the function during installation.
2. In case the function is not used, set the dip S/W OFF and reset the power.
3. If ODU RPM changes, cooling capacity may go down.
DIP Switch Settings
[Heater Pump] [Cooling only]
Warning : Please reset Main PCB before starting this function
Step Black Button Red Button
1 1 time 1 time
2 2 time 1 time
3 3 time 1 time
4 4 time 1 time
5 5 time 1 time
6 6 time 1 time
7 7 time 1 time
8 8 time 1 time
9 9 time 1 time