128
MULTI V IV System Installation Manual
Due to our policy of continuous product innovation, some specications may change without notication.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
Maximum allowable height differential (h) between two outdoor units is 16.4 feet.
Example of improper height differential.
Pipe Connections—Height Differential for Separated Outdoor Units
To indoor units
h≤16.4 feet
h≤16.4 feet
To indoor units
To indoor units
Oil Trap
≥11/16 inches
REFRIGERANT PIPING DESIGN