Refrigerant pipe diameter from branch to branch (B,C,D)
Downward Indoor Unit 
total capacity [kW(Btu/h)]
Liquid pipe [mm(inch)] Gas pipe [mm(inch)]
≤ 5.6(19,100)
Ø6.35(1/4) Ø12.7(1/2)
< 16.0(54,600) Ø9.52(3/8) Ø15.88(5/8)
≤ 22.4(76,400)
Ø9.52(3/8) Ø19.05(3/4)
< 36.4(124,200) Ø9.52(3/8) Ø22.2(7/8)
32
PIPE CONNECTIONS BETWEEN INDOOR AND OUTDOOR UNIT
ENGLISH
Refrigerant pipe diameter from outdoor unit to first branch. (A)
Outdoor unit
total capacity (HP)
Liquid pipe [mm(inch)] Gas pipe [mm(inch)]
2.5 Ø9.52(3/8) Ø15.88(5/8)
3 Ø9.52(3/8) Ø15.88(5/8)
4 Ø9.52(3/8) Ø15.88(5/8)
5 Ø9.52(3/8) Ø15.88(5/8)
6 Ø9.52(3/8) Ø19.05(3/4)
WARNING
When the any one (or both ) of below conditions are satisfied, the diameter of main pipe (A)
must be increased according to below table. 
- The equivalent length between outdoor unit and the farthest indoor unit is 90m or more 
(Liquid and Gas pipes are increased)
- The level difference (Outdoor unit ÷ Indoor unit) is 50m or more (Only liquid pipe is in-
creased) 
!