• * : Assume equivalent piping length of Y branch to be 0.5m, that of header to be 1m, calcu-
lation purpose
• Indoor Unit should be installed at lower position than the header.
WARNING
Pipe length after header branching (a~f)
It is recommended that difference in length of the pipes connected to the Indoor Units is
minimized. Performance difference between Indoor Units may occur. 
!
Outdoor unit capacity (HP) 2.5 3456
T
Total pipe length (m)
50 80 85 100 100
A+B+C+a+b+c+d+e
L
Longest pipe length (m) (Equivalent pipe length)
30 40 50 50 50
A+B+C+D+e
l
Longest pipe length after 1st branch (m)
20 30 30 30 30
B+C+D+e
H
Difference in height (m) (Outdoor Unit ÷ Indoor Unit)
15 15 15 15 15
H
h
Difference in height (m) (Indoor Unit ÷ Indoor Unit)
7.5 7.5 7.5 7.5 7.5
h