Trouble Shooting Guide
- 51 -
Copyright ©2013 LG Electronics. Inc. All right reserved.
Only for training and service purposes
LGE Internal Use Only
05 Bad communication
between main PCB
1 and main PCB 2.
53
• The connector for transmission is dis-
connected
• The connecting wires are miscon-
nected
• The communication line is broken
• Outdoor PCB is abnormal
• Indoor PCB is abnormal
• Wire connection between control panel
and main PCB 1 should be tight
Code
No.
Description Cause Normal Condition
Is main PCB 2 LED
blinking?
Yes 
Yes 
No 
Is main circuit breaker off?
No 
Check the main power 
supply at the unit
terminal block?
Improper connection of power supply cable 
Main power supply problem
Yes 
No 
Yes 
No 
Main PCB 2 fault
Replace after checking 
Re-connect transmission cable
No 
Yes 
Main PCB 1 fault
Replace after checking
Check the insulation of inverter
Check the capacity of main circuit 
breaker and replace if required
If all ok,
Turn on main circuit breaker
Replace main PCB 2 after
checking
Replace TRANS after checking
Check if the 
transmission cable is 
properly connected to 
terminal block of 
main PCB 1 and 
main PCB 2
Control panel 
displays CH05?
Replace main PCB 1
Reconnect transmission cable 
between main PCB 1 and control 
panel
n Error diagnosis and countermeasure flow chart
❊ CH05 is displayed at unit, 
     CH53 is displayed at outdoor unit.