Trouble Shooting Guide
- 54 -
Copyright ©2013 LG Electronics. Inc. All right reserved.
Only for training and service purposes
LGE Internal Use Only
15
Water pipe overheated
Code
No.
Description Cause Normal Condition
• Abnormal operation of
electric heater
• Leaving water temperature
is above 67 °C
• If there is no problem in electric heater
control, possible maximum leaving
water temperature is 62 °C.
Start
END
(it is normal
condition)
A
A
B
B
NO
YES
YES
YES
YES
NO
NO
Leaving water
temperature is higher
than target water
temperature
Thermostat is
installed
Leaving water
temperature is higher
than 62 °C
• This is unexpected case.
• Turn off the system and call service center.
• If the system is not turned off before it yields
error code (CH15), very hot leaving water will
be generated and it is harmful to human.
• Room air is not fully heated by under floor
heating.
• Wait while room air is heated by target
temperature of thermostat.