Trouble Shooting Guide
- 55 -
Copyright ©2013 LG Electronics. Inc. All right reserved.
Only for training and service purposes
LGE Internal Use Only
20 Electric Heater Overheated
Code
No.
Description Cause Normal Condition
• Abnormal operation of
electric heater
• Leaving water temperature
is above 90 °C
• If there is no problem in electric heater
control, possible maximum leaving
water temperature is 62 °C.
Start
END
(it is normal
condition)
A
A
B
B
NO
YES
YES
YES
YES
NO
NO
Leaving water
temperature is higher
than target water
temperature
Thermostat is
installed
Leaving water
temperature is higher
than 90 °C
• This is unexpected case.
• Turn off the system and call service center.
• If the system is not turned off before it yields
error code (CH20), very hot leaving water will
be generated and it is harmful to human.
• Room air is not fully heated by under floor
heating.
• Wait while room air is heated by target
temperature of thermostat.
• If Error Code (CH20) is occurred, please
check thermostat, electric heater, power
supply and others. Also, it is recommended
to check air vent which is located on the top
of the electric heater tank.

Other manuals for LG Therma V AHBW A0 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the LG Therma V AHBW A0 Series and is the answer not in the manual?

LG Therma V AHBW A0 Series Specifications

General IconGeneral
BrandLG
ModelTherma V AHBW A0 Series
CategoryAir Conditioner
LanguageEnglish

Related product manuals