System Set-Up
Installation Manual 79
ENGLISH
Code Item Detail Remark
05 Function Setting temperature selection
Description Selection for setting temperature as air temperature or
leaving water temperature.
Value #1 Note 01:Air temperature
02:Leaving water temperature
Air temperature as setting temperature is ONLY available
when remote air sensor.
Connection is enabled and Function code 03 is set as 02.
Default 2
Range 01 ~ 02
Value #2 Note -
Default -
Range -
06 Function Auto dry contact
Description
Setting dry contact auto start option.
If thermostat is used, value should be changed from "2" to "1".
Value #1 Note 01: Auto start off
02: Auto start on
Default 2
Range 01 ~ 02
Value #2 Note -
Default -
Range -
07 Function Address setting
Description Assigning address when central controller is installed
If thermostat is used, value should be changed from "2" to "1".
Value #1 Note -
Default 00
Range 00 ~ FF
Value #2 Note -
Default -
Range -
11 Function Setting air temperature in cooling mode
Description Adjusting range of 'Setting Air Temperature' in cooling mode
Value #1 Note Upper limit of setting range
Default 30 °C
Range 24 ~ 30 °C
Value #2 Note Lower limit of setting range
Default 18 °C
Range 18 ~ 22 °C
12 Function Setting leaving water temperature in cooling mode
Description Adjusting range of 'Setting Leaving Water Temperature' in
cooling mode
Value #1 Note Upper limit of setting range
Default 24 °C
Range 20 ~ 25 °C
'Setting Air
Temperature' is
used when user
wants to set target
temperature by
room air
temperature.
'Setting Leaving
Water Temperature'
is used when user
wants to set target
temperature by
leaving(from the
unit) water
temperature.