1.5 Storage and Transportation
• Keep the Liebert DCD in its original packaging, protected from the weather and in dry
conditions.
• Protect the unit’s working parts from sand, rain, dust and other particles and contaminants.
• Store at temperatures between -22°F and +122°F (-30°C and +50°C); the chilled water circuit
must be empty during storage.
• After storage for a year or longer, the water-bearing hinges must be inspected for functionality.
• Remove all packaging before starting the unit.
• Chilled water connections are not load-bearing and must not be used as handles.
• When transporting the Liebert DCD, always make sure the device is properly fastened and
secured against slipping.
WARNING! Risk of heavy module falling. Can cause equipment damage, injury and death.
Two properly trained and qualified people are required to move and install the module. The
Liebert DCD weighs 210lb. (95kg). It must be securely and properly fastened to the forklift or
pallet jack, if being used to move the unit.
NOTICE
Risk of a leaking coil due to freezing during improper storage. Can cause equipment and serious building
damage.
The heat exchanger and the supply pipes must be cleared of any water before the unit is stored, either
before storage or after removal from a cabinet. Compressed air can be used to remove the water. Remove
all the vents and the screws before storing.
Vertiv | Liebert® DCD™ User Manual | 6