Operating Ambient Temperature 50°F - 9F (1C - 35°C) (Other Temperatures on Request)
Maximum Absolute Air Humidity on Site 8g/kg
Chilled Water Temperature Intake 53.6°F (1C) Other Temperatures on Request
Chilled Water Temperature Outlet 64.4°F (18°C) Other Temperatures on Request)
Water Temperature Difference 10.8°F (6°K)
Use of Glycol On Request (Not Recommended)
Chilled Water Connection Rack - Rear Side (Top or Bottom Connection); 1" NPT
Condensate Tray Drain Connection Rack - Rear Side; 5/8"
Maximum Operating Pressure 145psi (10bar)
Table 3.1 Application conditions