Hiromatic controls the date and time functions using them as operating information for the customer and
as a reference whenever a status change occurs, causing the storage in the Report status. In addition,
details of the event which occurred and the date and time at which the event occurred are stored as well.
Thanks to the buffered RAM it is possible to store the operating hours of each component (compressor,
fan, electric heaters, humidifier) of the various interconnected units.
In addition to the date-time function, there is a function for stand-by unit rotation which can be activated
only by means of Hiromatic at a preset time of day. This is different from the Microface function, in which
the rotation occurs when 24 operating hours of one unit have been reached.
Finally, Hiromatic allows the Microface units to be integrated with Hirolink; for this purpose it is necessary
to install a RS422 card at the back of Hiromatic. In this way, Hiromatic can control up to 8 Microface units
and communicate the relevant data to Hirolink.
Serial communication
Integration
Hirolink is the key to the integration; it works as 'communication manager' between the
Hiromatic-Microface units and all the foremost supervision systems available on the market. It also
provides the link with Hirovisor supervision system, which is the ideal solution for all integration
requirements within the intelligent building. This permits local access to the units or, as an alternative,
modem connection to supervise several installations from a single remote point.
The components necessary for integration are shown in the picture above. The only 'variations' are the
software installed on Hirolink and the relevant hardware configuration which determines a different code.
11.20 -Deadening insulation coating
On request, a fiber glass insulation may be provided as heat and sound protection: a protective film and
a special gasket on the closing prevent particle dispersion and help the proper mechanical resistance of
the insulation. Some plastic gaskets fit on the panel hinder the air by-pass. The material is fully nonflam
mable and meets the requirements of the American norms NFPA90A and 90B concerning fire and smoke
prevention.
11.21 -Duct with deadening insulation coating
A special duct with nonflammable deadening insulation coating in compliance with the fire and smoke
prevention norms NFPA and 90B can be supplied on request.