Liebert.CRV Series Air Conditioner
User Manual
Version V1.4
Revision date May 28, 2012
BOM 31011886
Emerson Network Power provides customers with technical support. Users may contact
the nearest Emerson local sales office or service center.
Copyright © 2010 by Emerson Network Power Co., Ltd.
All rights reserved. The contents in this document are subject to change without notice.
Emerson Network Power Co., Ltd.
Address: No.1 Kefa Rd., Science & Industry Park, Nanshan District 518057, Shenzhen
China
Homepage: www.emersonnetworkpower.com.cn
E-mail: support@emersonnetwork.com.cn

Table of Contents

Questions and Answers

  • N
    Nicole WebbAug 18, 2025
    What to do if Liebert Air Conditioner has high pressure protection?
    • A
      Angela BradleyAug 18, 2025
      If the Liebert Air Conditioner experiences high pressure protection, it could be due to a clogged condenser. Clean the condenser. If it is an air-cooled system, check the condensing fan. Also, too much refrigerant may have been charged. Check whether the subcooling degree is too high.
  • B
    Brian JonesAug 20, 2025
    What to do if contactor does not close and Liebert CR035 Air Conditioner compressor does not start?
    • K
      Kimberly BooneAug 20, 2025
      If the contactor does not close and the Liebert Air Conditioner compressor does not start, check the state of the micro-processing controller. Inspect the high pressure MCB for high pressure alarm. Check for discharging low/high temperature alarms. View the history alarm for a low pressure alarm. Check the contactor and the compressor driver. Check if the compressor coil is open circuit. If so, wait till the coil is cooled and it will be restored automatically.
  • S
    sarah62Aug 23, 2025
    What to do if Liebert CR035 contactor closes, but heating is ineffective?
    • C
      cainstevenAug 23, 2025
      If the contactor closes but the heating is ineffective in your Liebert Air Conditioner, first check that the heating MCB is closed and that the power voltage of contactor L1, L2, L3 is normal. If the issue persists, cut off the power supply and measure the resistance of the heater with an ohmmeter to determine if the electric heater is damaged.
  • I
    iwintersAug 26, 2025
    Why Liebert Air Conditioner compressor does not start?
    • L
      Lisa GarciaAug 26, 2025
      If the Liebert Air Conditioner compressor doesn't start, several factors could be at play. First, check the main power supply for undervoltage, overvoltage, or phase loss. Then, inspect the compressor's MCB, contactor, and connecting cables. Review the unit's alarm records, replace any damaged components, and power it on again. Finally, examine the motor for shorted and burnt coils, replacing it if necessary.
  • S
    Sandra EspinozaAug 28, 2025
    What to do if Liebert CR035 compressor stops after 3 minutes?
    • B
      Brandon SmithAug 28, 2025
      If your Liebert Air Conditioner's compressor stops after running for only 3 minutes and the contactor opens, it could be due to a refrigerant leak causing low pressure. First, check the suction pressure. Second, inspect the low pressure sensor's circuit. Finally, calibrate the low pressure sensor reader to ensure it's within ±0.3bar of the actual pressure.
  • C
    Charles ShafferAug 30, 2025
    Why is Liebert Air Conditioner compressor too noisy?
    • K
      Kathryn CarpenterAug 30, 2025
      If the Liebert Air Conditioner's compressor is too noisy, it could be due to liquid returning into the compressor or worn-out bearings. Refer to the troubleshooting steps for 'Low suction pressure or liquid returned.' Also, try adding lubricant to the compressor.
  • L
    Logan GriffinSep 2, 2025
    How to troubleshoot Liebert CR035 Air Conditioner EC fan that does not start?
    • K
      Kimberly AnthonySep 2, 2025
      If the EC fan of your Liebert Air Conditioner doesn't start, first check that the fan MCB is closed and that the power voltage of each phase is normal. If the issue persists, check J15 on the micro-processing control board to determine if the control board is faulty. Then, inspect the alarm lamp on the fan power module to see if it is faulty. Finally, check L1, L2, and L3 of the fan for power failure, phase loss, and low voltage; confirm that the analog output is within 0 ~ 10Vdc; check for motor clogging or overheating; and check for Hall failure.
  • C
    Charles HuertaSep 4, 2025
    Why is Liebert CR035 compressor over-temperature?
    • S
      Sarah HuertaSep 4, 2025
      If the Liebert Air Conditioner's compressor is overheating, it could be caused by a high compression ratio or a high suction overheat degree. Check the settings of the HP and LP switches, and ensure the condenser is not clogged. Verify that the evaporator and condenser fans are functioning normally. Regulate the electronic expansion valve or add the correct amount of refrigerant.
  • M
    Michaela TateSep 7, 2025
    What causes low suction pressure or liquid returned in Liebert CR035 Air Conditioner?
    • J
      julieeatonSep 7, 2025
      If your Liebert Air Conditioner has low suction pressure or liquid is returning, it could be due to several reasons. First, check for refrigerant leaks, seal any leaks, and add refrigerant. Second, replace the air filter if it's dirty. Third, replace the filter drier if it's clogged. Fourth, check the control board of the electronic expansion valve for improper superheating degree. Fifth, replace the sensing element if the electronic expansion valve is faulty. Sixth, check the air supply and return system for improper air flow distribution. Finally, check whether the condenser is faulty, which could cause low condensing pressure.
  • D
    Donna ReyesSep 9, 2025
    Why Liebert CR035 heating system does not start?
    • M
      Michael AlexanderSep 9, 2025
      If the heating system of your Liebert Air Conditioner doesn't start and the contactor doesn't close, it could be due to a lack of heating demand or an open safety device. Check the state of the micro-processing controller to confirm if a heating command is required. Use a multimeter to measure the resistance on both ends of the temperature controller; if the resistance is very large, the safety device may be open. Then check if the fuse is open and if the temperature controller is damaged. Measure the resistance of the heater with an ohmmeter to judge if the heater is damaged.

Summary

Important Safety Instructions

Warning - Risk of top-heavy unit falling over

Instructions for safe movement and handling to prevent serious injury or equipment damage.

Caution - Risk of sharp edges, splinters and exposed fasteners

Safety precautions for personnel handling the unit, emphasizing proper protective gear.

Caution - Risk of overhead interference

Warning about potential unit and structure damage due to overhead obstructions during movement.

Warning - Risk of electric shock

Critical safety advice regarding electrical hazards and required disconnects before maintenance.

Warning - Risk of explosive discharge from high-pressure refrigerant

Safety alert about high-pressure refrigerant hazards and pressure relief procedures.

Warning - Risk of refrigerant system rupture or explosion from overpressurization

Safety measures for preventing overpressurization in the refrigerant system.

Digit Nomenclature

Chapter 1 Preliminary Operations

1.3 Operating Limits

Specifies the operational ranges for temperature, humidity, and power supply.

Chapter 2 Unit Positioning

1. Placement in the row of racks

Guidance on optimal placement of units within rack rows for best performance.

3. Placement in the room

Guidance on room placement, specifically cold aisle and hot aisle width.

5. Example of applications with CoolFlex

Recommendations for using CoolFlex with Liebert.CRV for high density IT loads.

6. Example of applications with Liebert XD

Integration examples of Liebert.CRV with Liebert XD systems for high density and scalability.

Chapter 3 Unpacking And Installation

3.1 Reference Guide For Receiving, Unpacking, And Preparing For Installation

Comprehensive guide for receiving, unpacking, and preparing the unit for installation.

3.4 Unpacking The Unit

Step-by-step procedure for safely unpacking the Liebert.CRV unit.

3.5 Installation

Steps for installing the unit, including opening panels and checking serial numbers.

Chapter 4 Refrigeration Connections

4.1 Refrigeration Pipeline Connections For Air-Cooled (A) Units

Details on connecting refrigeration pipelines for air-cooled units.

4.1.3 Installing Pipelines

Detailed steps for installing refrigeration pipelines by a qualified technician.

4.2 Vacuum Creation And Refrigerant Charge

Procedure for vacuum creation and charging refrigerant into the system.

4.2.1 R410 A Precharge For Air-Cooled (A) Units

Specific steps for pre-charging R410A refrigerant into air-cooled units.

4.2.2 Refrigerant Charge For Air-Cooled (A) Units

Procedure for charging refrigerant into air-cooled units for normal operation.

Chapter 5 Water Connections

5.1 General Warning

Warning about adding glycol to the circuit for outdoor tubing.

5.2 Water Connections - Supply Humidifier And Drain Water (All Units)

Details on water connections for humidifiers and condensate drain for all unit types.

5.3 Chilled Water Connections For Water;Glycol-Cooled (W) Units

Instructions for connecting chilled water to water/glycol-cooled units.

5.4 Chilled Water Connections For Chilled Water (C) Units

Instructions for connecting chilled water to chilled water units.

Chapter 6 Electrical Connections

Chapter 7 Start-Up

7.1 First Start-Up (Or After Long Standstill)

Detailed steps for initial startup, including preheating and checks.

Chapter 9 Calibrations & Regulation (At Start-Up)

9.1 Setting Thermostatic Expansion Valve

Procedure for adjusting the thermostatic expansion valve for proper superheat.

Chapter 10 Maintenance & Spare Parts

10.1 Safety Instructions

Essential safety guidelines for performing maintenance operations.

10.8.1 Refrigerant Charge Of The Water-Cooled Units

Steps for charging refrigerant into water-cooled units.

10.11 Unit Diagnostic

Table of common problems, their possible causes, and corrective actions.

Appendix 4 Refrigerant, Hydraulic And Electrical Connections

Liebert CR035 Specifications

General IconGeneral
BrandLiebert
ModelCR035
CategoryAir Conditioner
LanguageEnglish