Hiflex
18 All Versions
English
Performances Electric data Overall dimensions
Low Noise
Model
Duty(
a
) Air flow
SPL
10 m (c)
Supply
Number of
fans
Total
absorbed
power
Width Depth Height (
b
)
kW m
3
/h db(A) V/ph/Hz nº kW mm mm mm
DLM008 7.5 4.700 39 230/1/50 1 0.29 1250 900 990
DLM011 10.5 3.700 39 230/1/50 1 0.29 1250 900 990
DLM015 15.5 9.500 42 230/1/50 2 0.58 2.050 900 990
DLM018 18 9.000 42 230/1/50 2 0.58 2.050 900 990
DLM023 23 14.000 43 230/1/50 3 0.87 2.850 1260 990
DLT027 27.5 15.000 47 400/3/50 2 0.7 2.750 1260 1.140
DLT030 30 14.500 47 400/3/50 2 0.7 2.730 1260 1.140
DLT040 40 22.500 49 400/3/50 3 1.05 3.900 1260 1.140
DLT047 47 21.750 49 400/3/50 3 1.05 3.900 1260 1.140
DLT055 54 20.250 49 400/3/50 3 1.05 3.900 1260 1.140
DLT065 65 29.000 50 400/3/50 4 1.4 5.060 1260 1.140
DLT085 84 40.500 54 400/3/50 3 2.16 5.010 1.640 1.500
DLT110 112 54.000 55 400/3/50 4 2.88 6.520 1.640 1.500
DLT130 130 67.000 51 400/3/50 4 3.72 6.520 1.640 1.570
DLT160 157 62.000 51 400/3/50 4 3.72 6.520 1.640 1.570
DLT190 190 77.500 52 400/3/50 5 4.65 8.055 1.640 1.570
DLT210 212 123.000 54 400/3/50 8 7.44 6.155 2.420 1.570
DLT250 253 132.000 51 400/3/50 8 6.88 7.355 2.440 1.770
DLT270 270 153.750 55 400/3/50 10 9.3 7.555 2.420 1.770
DLT290 290 118.000 51 400/3/50 8 6.88 7.355 2.440 1.770
DLT310 310 137.500 55 400/3/50 10 9.3 7.555 2.420 1.570
DLT350 350 147.500 52 400/3/50 10 8.6 9.055 2.440 1.770
(a): at the following conditions: outdoor temperature = 35°C, inlet/outlet water temperature = 45°C/40°C.
(b): vertical flow installation.
(c): according to DIN45635.