Hiflex
55-W- Version
English
Technical data and performances-water condensation -xxUW series, downward flow-50Hz
MODEL 4PUW 4GUW 6PUW 6GUW 8PUW 8GUW
power supply voltage V/ph/Hz 400/3/50 400/3/50 400/3/50 400/3/50 400/3/50 400/3/50
PERFORMANCES
(1)
air flow m
3
/s 0.46 0.64 0.74 0.80 1.21 1.31
available head Pa 20 20 20 20 20 20
fan absorbed power kW 0.3 0.6 0.4 0.5 0.9 1.2
fan absorbed current A 1.4 2.6 2.6 3.3 4.5 5.4
sound pressure level
(2)
dB(A) 46.9 50.1 50.0 51.3 50.3 52.6
condenser inlet water temperature: 15°C; condensation temperature: 40°C
total cooling capacity kW 5.8 8.7 10.7 12.8 14.1 17.1
sensible cooling capacity kW 5.1 7.4 9.3 11.1 13.9 15.5
full absorbed power (fan and compressor) kW 1.6 2.5 2.6 3.2 3.7 4.7
compressor absorbed power kW 1.3 1.9 2.2 2.8 2.8 3.4
compressor absorbed current A 6.1 3.9 4.4 5.6 5.7 7.2
SHR (Sensible Heat Ratio) - 0.88 0.85 0.87 0.86 0.99 0.91
EER (Energy Efficiency Ratio) - 3.60 3.53 4.12 4.00 3.84 3.67
water flow l/s 0.05 0.09 0.09 0.12 0.13 0.17
water pressure drop kPa 1 2 1 2 2 3
condenser inlet water temperature: 30°C; condensation temperature: 45°C
total cooling capacity kW 5.6 8.3 10.2 12.2 13.4 16.3
sensible cooling capacity kW 5.0 7.2 9.1 10.8 13.4 15.2
full absorbed power (fan and compressor) kW 1.8 2.7 2.9 3.6 4.0 5.0
compressor absorbed power kW 1.5 2.2 2.5 3.1 3.1 3.8
compressor absorbed current A 6.8 4.2 4.8 6.0 6.0 7.6
SHR (Sensible Heat Ratio) - 0.90 0.87 0.89 0.88 1.00 0.93
EER (Energy Efficiency Ratio) - 3.12 3.07 3.55 3.45 3.33 3.23
water flow l/s 0.11 0.20 0.20 0.27 0.30 0.40
water pressure drop kPa 3 10 4 6 8 14
FANS
quantity no. 1 1 1 1 1 1
type - dd 9/9 dd 9/9 dd 10/10 dd 10/10 dd 12/12 dd 12/12
speed no. 3 3 3 3 3 3
nominal power kW 0.245 0.420 0.500 0.500 0.736 0.736
poles no. 6 4 6 6 6 6
COMPRESSOR
quantity/type 1/scroll
nominal power for each compressor HP 1.90 2.50 3.25 4.00 4.00 5.00
refrigerant R407C R407C R407C R407C R407C R407C
EVAPORATING COIL
pipes/fins copper/aluminium copper/treated aluminium
fins for inch/rows no. 12/3 12/3 12/4 12/4 12/5 12/5
front surface m
2
0.33 0.33 0.50 0.50 0.50 0.50
position/quantity inclined/1
CONDENSER
quantity/type - 1/plate
water connections inch ½" BSP
DIMENSIONS
length mm 750 750 750 750 750 750
depth mm 450 450 600 600 750 750
height mm 1950 1950 1950 1950 1950 1950
plan surface m
2
0.34 0.34 0.45 0.45 0.56 0.56
WEIGHTS
net kg 185 200 210 225 285 300
gross kg 195 210 220 235 295 310
1 ON THE FOLLOWING STANDARD CONDITIONS: standard supply [voltage 10%]; room conditions 24°C bs; 50% R.H. (17°C bu)
2 Measured in the front part at 1 m height, 2 m distance, referred to free field, with working fans and compressor.
ATTENTION: the refrigerating outputs are meant after deduction of the heat taken from the fans, which must thus be added to the room load. The EER
refers only to the room unit. The unit air flow refers in standard configuration with clean class filter G3.