Liebert PSA itON Installation and User Manual
6. Technical Data
600VA 1000VA
CAPACITY V/AW 600VA/360W 1000VA/600W
Voltage Range 140-300 VAC 160-300 V
Frequency 45-65 Hz (Auto Sensing) 45-65 Hz (Auto Sensing)
Voltage Range 230V 230V
Voltage Regulation
(
Batt Mode
)
+/-10% +/-5%
Frequency 50Hz or 60Hz 50Hz or 60Hz
Frequency Regulation
(Batt Mode)
+/-1Hz +/- 1 Hz
Output Waveform Stepped Waveform Stepped Waveform
Overload
110% for 5 minutes as 'Mains'
mode
110% for 5 minutes as 'Mains'
mode
Battery Type &
Number
12V/7AH - 1Pc 12V/7AH - 2 Pcs
Backup time (*As per
the loads)
15-22* mins 30 min typical* (with 1 PC)
Recharge Time
8 hours to 90% after complete
discharge
8 hours to 90% after complete
discharge
TRANSFER TIME Typical 4-8 ms 4-8 ms
AC Mode Green Lights up
Green Lights Up
The 1st green lighting up, the
2nd to 5th green lighting up
indicates load ca
p
acit
y
Backup Mode Green Flashes
Green Flashes
The 1st green flashing, the 2nd
to 5th green gradually lighting
indicates batteries ca
p
abilit
y
Fault Red Lighting up
Backup Mode Sounds every 10 seconds Sounds every 10 seconds
Low Battery Sounds every second Sounds every second
Overload Sounds every 0.5 seconds Sounds every 0.5 seconds
Battery Replacement Sounds every 2 seconds Sounds every 2 seconds
Fault Continuously Sounding Continuously Sounding
PROTECTION Full Protection
Discharge, overcharge and
overload
p
rotection
Discharge, overcharge and
overload
p
rotection
Dimension (m,m)
DxWxH
330 x 100 x 140 369x141x181
Net Weight 6 kg 13.5 kg
Operating Environment
0-40 C 0-90% relative humidity
(
non condensin
g)
0-40 C 0-90% relative humidity
(
non condensin
g)
Noise Level Less than 40 db Less than 40 db
INTERFACE RS 232
Support Windows
95/98/NT/2000/XP and Linux
Support Windows
95/98/NT/2000/XP and Linux
*For additional information on backup please contact your local Emerson Network Power representative
PHYSICAL
ENVIRONMENT
Liebert PSA itON
AUDIBLE ALARM
BATTERY
INDICATOR
INPUT
OUTPUT
Page 12 V2.8 Emerson Network Power
PS600-TN PS1000-TN