Operation Status and LED Indicators
10
LED
Status
Operation
Status
Possible
Cause
Resolution
the cable connection
and check the
termination resistor
configuration.
A master device does
not exist in the network.
A master device has
not been assigned,
or the master
device's station ID
has been set
incorrectly.
Station ID has been set
incorrectly.
In the configuration
tool, check if the
station ID assigned
for the
communication
module is identical to
the station ID set
from the inverter's
(using the keypad
input). Then, ensure
that the station ID is
not duplicated in the
network.
Network Configuration
Error
Check if the network
cable length of the
segment exceeds
the maximum
allowed length.
Check if the segment
has more than 32
stations (including a
repeater). Check if
the network has
more than 126
stations (including a
repeater).
On
Online
All settings (network
and station ID settings,
parameters, and
configuration) are
normal.
Table 6 Device Status by Indicator Signals