4.2.5 Para Status 1–8
The following parameters are used to set the Station ID for the PROFIBUS-DP
communication module.
Number of Para Status settings
The "Para Status" setting defines which status information will be sent to the master
device through PROFIBUS-DP network communication.
Para Status 1–8 are set in the form of inverter address.
The inverter's common area and keypad parameter addresses are used as the setting
values.
The keypad parameter addresses can be expressed according to the following
formula: 0x1000 + ("Group number" x 0x100) + ("Code number").
For example, if you want to set "Para Status1" to "In.90 (DI Status)," you can set it as
an address, "0x155A."
0x1000 + 0x05 x 0x100 + 0x5A (Dec 90) = 0x155A
SPS Group (Operation Group)