4.2.6 Number of Para Control settings
Number of Para Control settings
Para Control 1–Control 8 settings
The parameters above are used to determine how much "Para Control" data will be
sent to the master device by the inverter through PROFIBUS-DP network
communication.
The number of the "Para Control" can be set to a number between 0 and 8.
After setting the number of "Para Control", each "Para Control" has to be set using the
matching number of parameters from CM-51 to CM-58. For example, if CM-50 is set
to "2," "Para Control" should be set for CM-51 to CM-52. If CM-50 is set to "5," the
"Para Status" should be set for CM-51 to CM-55.
After changing the number of "Para Control," you must set "CM-94 (Comm Update)"
to "1" to apply the changes to the PROFIBUS-DP communication module.