17
4.2.7 Para Control 18
CM-50
Number of Para Control settings
CM-51
~
CM-58
Para Control 1Control 8 settings
The "Para Control" setting defines which control information will be sent to the master
device through PROFIBUS-DP network communication.
Para Control 18 are set in the form of an inverter address.
The inverter's common area and keypad parameter addresses are used as the setting
values.
The keypad parameter addresses can be expressed according to the following
formula: 0x1000 + ("Group number" x 0x100) + ("Code number").
For example, if you want to set the jog frequency set "Para Control 1" to "dr-11 (Jog
frequency)," you can set it as an address, "0x110B."
0x1000 + 0x01 x 0x100 + 0x0B (Dec 11) = 0x110B
Group
Group Number
dr Group
1 (0x01)
bA Group
2 (0x02)
Ad Group
3 (0x03)
Cn Group
4 (0x04)
In Group
5 (0x05)
OU Group
6 (0x06)
CM Group
7 (0x07)
AP Group
8 (0x08)
(Reserved)
9 (0x09)
(Reserved)
10 (0x0A)
PRT Group
11 (0x0B)
M2 Group
12 (0x0C)
SPS Group (Operation Group)
13 (0x0D)