Chapter 6. Input and Output Specifications
6-13
6.3.3 Main unit (PNP TR output)
1) Specifications
Main Unit
Model
Specifications
G7M-DT20U(P)(/DC) G7M-DT30U(P)(/DC) G7M-DT40U(P)(/DC) G7M-DT60U(P)(/DC)
Output point 8 points 12 points 16 points 24 points
Insulation method Photo coupler insulation
Rated load voltage DC12/24V
Operation load voltage DC10.2 ~ 26.4V
Max. load current
0.5A/point (but, QX0.0.0, QX0.0.1 : 0.1A)
Surge absorber Zener diode
Off leakage current Less than 0.1mA
Voltage drop when on Less than DC 0.3 V (0.1A)
Inrush current Less than 4A, 10ms
Off → On 0.2 ms or lower Response
time
On → Off 0.2 ms or lower
Operation indicator LED is on at on status of output
QX0.0.2 , QX0.0.3
QX0.0.0 , QX0.0.1
1) 4 points of QX0.0.0~QX0.0.3 are for positioning function in G7M-DT20/30/40/60U(P)(/DC). They also can be used for
general TR output.
2) Do not use for AC load, or they can be destroyed.
REMARK