Chapter 7. Usage of Various Functions
7-27
(2) Auto tuning function block (PID7AT)
Function block Description
Input
EN: enables PID7CAL function block (Level operation)
LOOP: sets execution loop (0~7)
Output
DONE : Turn on whenever the auto tunin
g
operation is completed.
END : Turns on when the F/B operation is completed with no error, and
keep the status until next F/B execution.
STAT Displays the error code
MV: The manipulated value of current loop on which the auto tunin
g
operation is performed.
P: The proportional gain constant obtained by auto tuning operation.
I: The integral time constant obtained by auto tuning operation.
D: the derivative time constant obtained by auto tuning operation.
a) Usage
When the condition of the execution is On, PID auto tuning operation executes and calculates P,I,D constant.
LOOP No. (LOOP) designates the LOOP no. that is registered at the PID auto tuning parameter. (0~7)
Stat disignates the area where the PID auto tuning loop’s status is saved.
b) Program example
When the input condition %IX0.0.0 turns On, the auto
tuning starts its operation following the parameter 0.
During the auto tuning, DONE state keeps On, and when
it finished END state turns On.
When an error occurs the STAT is ouputted at %MB100.
MV is saved in %MW10.
The P,I,D values are saved in %MW11,%MW12,%MW13
respectively.