EasyManua.ls Logo

LS Industrial Systems GLOFA G7M-DR30U - System error flag lists

LS Industrial Systems GLOFA G7M-DR30U
367 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Appendix 2. Flag Lists
App2-2
2) System error flag lists
Keyword Type Bit No. Name Description
_CNF_ER WORD
Represent--
ative
keyword
System error
(fatal error)
This flag handles the following operation stop error flags in
batch.
_IO _DEER BOOL Bit 2
Module
loading/unload
ing error
This representative flag indicates that module configuration of
each slot has been changed during operation. (Refer to
_IO_DEER_N and _IO_DEER[n])
_IO _RWER BOOL Bit 4
I/O module
read/write
error
This representative flag indicates that a I/O module does
normally executes read/write. (Refer to _IP_RWER_N and
_IP_IFER[n])
_SP _IFER BOOL Bit 5
Special/com-
munications
module
interface error
This representative flag indicates that special or communications
module has failed in initialization or normal interface is
impossible due to module malfunction. (Refer to _IP_IFER_N
and _IP_IFER[n])
_ANNUN_ER BOOL Bit 6
External
device fatal
fault detection
error
This representative flag indicates that an external device has
fatal error. The error code has been written to _ANC_ERR[n].
Bit 7
_WD_ER BOOL Bit 8
Scan watch
dog error
This flag indicates that the scan time of a program has overrun
the scan watchdog time specified by the parameter.
_CODE_ER BOOL Bit 9
Program code
error
This flag indicates that an unreadable instruction has been met
while executing an user program.
_STACK_ER BOOL Bit 10
Stack overflow
error
This flag indicates that the stack is used out of its
capacity(Overflow)
_P_BCK_ER BOOL Bit 11 Program error
This flag indicates that program execution is impossible due to
destroyed memory or program error.

Table of Contents