7. Function List
I60 [Inverter
station
number]
1/32
This parameter is set when the
communication.
1 O
I61 [Baud rate]
0/4
Select the Baud rate of the
RS485
3 O
0 1200 bps
2 4800 bps
4 19200 bps
I62 [Drive mode
select after
loss of
frequency
command]
0/2
It is used when frequency
command is given via V1 and I
terminal or communication
option.
0 O
0 Continuous operation
1
Free Run stop (Coast to
stop)
2 Decel to stop
I63
frequency
command]
[sec]
This is the time inverter
determines whether there is the
input frequency command or not.
If there is no frequency command
input during this time, inverter
starts operation via the mode
selected at I62.
1.0
-