Lucent Technologies Galaxy Power System 4812
Issue 5 June 2000 Troubleshooting Millennium Systems 13 - 17
BD and RM Alarm
LEDs, or No LED
Table 13-F: Miscellaneous Alarms
Controller
LED
Controller
Alarm
Status
Millennium
Controller Display
Other
Indication(s)
Possible
Problem(s)
Possible Solution(s)
BD MAJ Battery on
Discharge
Rectifiers
may say
ACF.
Temporary
condition that
may be
associated with
other alarms
Call your local RTAC
representative.
RM MIN Module Failure Green LED
on RPM will
not blink.
Remote
Peripheral
Module has
failed.
Call your local RTAC
representative.
RM MIN Measurement Out
of Range
-- •Data being
sensed exceeds
remote
peripheral
module’s
capability.
•Remote
peripheral
module has
failed.
Call your local RTAC
representative.
None MAJ Auxiliary Major Auxiliary
equipment
may have
alarm.
Problem with
operation of
auxiliary
equipment
Call your local RTAC
representative.
None MIN Auxiliary Minor Auxiliary
equipment
may have
alarm.
Problem with
operation of
auxiliary
equipment
Call your local RTAC
representative.
None None None •STBY LED
on rectifier
is lit.
•TR on
rectifier
display
Remote transfer:
•Rectifier is in
STBY.
Remove the remote standby
command issued by the
controller.
None None None Red LED is
lit on some
battery
contactor
drive boards,
while green
LED is lit on
others.
If a green LED is
lit despite a
contactor open
command issued
by the controller,
the drive card or
the contactor has
failed.
Call your local RTAC
representative.