Lucent Technologies Galaxy Power System 4812
Issue 5 June 2000 DC Distribution Panels 7 - 1
7 DC Distribution Panels
Overview
Function A variety of dc distribution panels is available for the GPS 4812 system,
including DIN standard fuse holders and circuit breakers and U. S.
standard fuse holders and circuit breakers. All panels are equipped with
an alarm card. When a fuse operates or a circuit breaker trips, a red LED
on the alarm card lights, the cabinet alarm lights, and the alarm is
transmitted to the controller. Most panels are also available with
contactors to provide low voltage load disconnect.
Illustrations The dc distribution panels are illustrated in Figures 7-1 through 7-14.
Note: DC distribution panels are white; battery connection panels are
blue.